| Description | Parameters |
|---|---|
| Input Supply | |
| Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 3/4 wire system |
| Variation | +/- 10% |
| Frequency | 50Hz /60Hz +/- 5Hz |
| Power Factor | Better than 0.93 Lag |
| DC Output | |
| Nominal Voltage | 110V 220V |
| Operating Voltage | 121A/242V |
| Static Voltage Regulation | ± 1% |
| Rating | 25A/50A/150A |
| Ripple | ≤ 1% RMS |
| Over load Capacity | 110% |
| Charging Characteristics | As per customer requirement. (according to DIN41773) |
| Efficiency | Better than 90% |
| Control Mode | Constant current/voltage/power |
| Duty Ratio | Continuous operation at rated load |
| Operation mode | Local/remote |
| System & Environmental | |
| Isolation | Input/Output HF transformer |
| Cooling | Natural / Forced Air |
| Protection Class | Upto IP54 (IEC 60529) |
| Ambient Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise | ≤65 dB NES 537 |
| Relative humidity | 15%-85%RH |
| User Interface | |
| Communication interface | RS485, 0-10V/4-20mA |
| Communication protocol | MODBUS, Profibus, Profinet, TCP/IP |
| Process programming | Available |
| Polarity reversal | Forward /Reverse |
| Module separate output | Available |
| Parallel connection module number | No limit |
| Remote control box | Available |
| Spare parts | Available |
| HMI | Touch panel or digital meters/buttons |
| Dimensions in mm | 600 x 400 x 1500 |
| Weight | 95kg Approx |
| Finishing | RAL7035 |
- 25A
- 50A
- 75A
- 100A
- 150A
- 200A
- 300A
- 400A
- 500A
- 600A
- 800A
- 1000A
- 1250A
- 1500A
- 2000A
- 3000A
- 5000A
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 25A |
| Input | |
| Nominal Voltage | 230V AC single Phase |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 1800 mm Width and Depth vary with Voltage and current rating |
| Ratings | 25A |
| Output Voltage | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| Cooling | Natural Air |
| Efficiency | 80% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 42 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 50A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 1800 mm Width and Depth vary with Voltage and current rating |
| Ratings | 50A |
| Output Voltage | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| Cooling | Natural Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 42 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 75A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 1800 mm Width and Depth vary with Voltage and current rating |
| Ratings | 75A |
| Output Voltage | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| Cooling | Natural Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 42 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 100A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 1800 mm Width and Depth vary with Voltage and current rating |
| Ratings | 100A |
| Output Voltage | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| Cooling | Natural Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 42 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 150A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 1800 mm Width and Depth vary with Voltage and current rating |
| Ratings | 150A |
| Output Voltage | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| Cooling | Natural Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 42 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 200A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 1800 mm Width and Depth vary with Voltage and current rating |
| Ratings | 200A |
| Output Voltage | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| 600 x800 | |
| Cooling | Natural Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 42 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 300A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 1800 mm Width and Depth vary with Voltage and current rating |
| Ratings | 300A |
| Output Voltage | |
| 600 x800 | |
| 800 x 800 | |
| 800 x 800 | |
| 800 x 800 | |
| Cooling | Forced Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 20 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 400A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 1800 mm Width and Depth vary with Voltage and current rating |
| Ratings | 400A |
| Output Voltage | |
| 800 x 800 | |
| 800 x 800 | |
| 800 x 800 | |
| 1000 x 800 | |
| Cooling | Forced Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 20 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 500A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 1800 mm Width and Depth vary with Voltage and current rating |
| Ratings | 500A |
| Output Voltage | |
| 800 x 800 | |
| 800 x 800 | |
| 1000 x 800 | |
| 1200 x 800 | |
| Cooling | Forced Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 20 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 600A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 1800 mm Width and Depth vary with Voltage and current rating |
| Ratings | 600A |
| Output Voltage | |
| 800 x 800 | |
| 800 x 800 | |
| 1000 x 800 | |
| 1000 x 800 | |
| Cooling | Forced Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 20 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 800A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 2100 mm Width and Depth vary with Voltage and current rating |
| Ratings | 800A |
| Output Voltage | |
| 800 x 800 | |
| 1000 x 800 | |
| 1000 x 1000 | |
| 1000 x 1000 | |
| Cooling | Forced Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 20 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 1000A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 2100 mm Width and Depth vary with Voltage and current rating |
| Ratings | 1000A |
| Output Voltage | |
| 1000 x 800 | |
| 1000 x 800 | |
| 1000 x 1000 | |
| 1000 x 1000 | |
| Cooling | Forced Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 20 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 1250A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 2100 mm Width and Depth vary with Voltage and current rating |
| Ratings | 1250A |
| Output Voltage | |
| 1000 x 800 | |
| 1000 x 800 | |
| 1000 x 1000 | |
| 1000 x 1000 | |
| Cooling | Forced Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 20 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 1500A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | ≤ 120% for 20mts, ≤ 150% for 2mts, ≥ 150% for 20 secs |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 2100 mm Width and Depth vary with Voltage and current rating |
| Ratings | 1500A |
| Output Voltage | |
| Cooling | Forced Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 20 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 2000A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 2100 mm Width and Depth vary with Voltage and current rating |
| Ratings | 2000A |
| Output Voltage | |
| Cooling | Forced Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 20 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 3000A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 2100 mm Width and Depth vary with Voltage and current rating |
| Ratings | 3000A |
| Output Voltage | |
| Cooling | Forced Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 20 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |
DC Power Supplies for lifting magnets are available in both a fixed voltage output (usually 220 VDC or 115 VDC) and a variable output (usually 0-220 VDC or 0-300 VDC). Fixed voltage output type DC Power Supplies are used in most general magnet applications. Variable voltage supplies are used in applications of fanning, boost/carry, flux reduction, constant flux regulation, etc.
- The IGBT/SMPS based Rectifier conversion technique with digital control.
- The system reduces the grid pollution by mitigating the input harmonics and improving the input PF to near to unity
- Excellent Transient Response & Recovery.
- Advanced Battery Charging Management
- Highly customizable system with user defined
- Diagnostics & Monitoring Facility
- Highly customizable system
- RS485 Remote Monitoring Features
- Advanced communication options.
| Technical Specification | Float cum Boost Charger |
| Ratings | 5000A |
| Input | |
| Nominal Voltage | 380V / 440V / 480V /690V AC Three phase 3 wire, 4 wire system |
| Frequency | 50 /60 Hz ±5 Hz |
| Input THDi | 27% -6P; 12% – 12P; 6% THD Filter +12P |
| Output | |
| Nominal Voltage | 24 /48 /110 /220 V DC |
| Operating Voltage | Float: 2.27V per cell( VRLA); 1.4-1.5V per cell (NiCd) Adjustable; Boost : 2.4 – 2.45V per cell (VRLA); 1.65v PER CELL (NiCd); Equalizing: Upto 2.35V per cell (VRLA); Upto 1.7V per cell (NiCd) Adjustable. |
| Static Voltage Regulation | ± 1% |
| Ripple | ≤ 1% |
| Overload Capacity | |
| Charging characteristic | As per customer requirement. (according to DIN41773) |
| System and environmental | |
| Isolation | Input /Output |
| Dimensions Wx D( in mm ) | Height is 2100 mm Width and Depth vary with Voltage and current rating |
| Ratings | 5000A |
| Output Voltage | |
| Cooling | Forced Air |
| Efficiency | Better than 93% |
| Colour | RAL7035 |
| Degree of Protection(IEC60529) | IP 20 |
| Operating Temperature | – 10 Deg C to +50 Deg C |
| Storage Temperature | – 20 Deg C to +70 Deg C |
| Altitude | ≤ 2000 m ( Derating according to IEC 62040-3) |
| Audible Noise at 1mtr | ≤65 dB |
| Options | Dropping cells or DC/DC chopper Convertor, Built in battery breaker, Battery Thermal Probe, Blocking Diode, Electronic Load Sharing for Parallel operation,Earth Fault alarm. |
| User Interface | |
| Front Panel | LCD display , LED Mimic, keyboard,status and alarm LED set |
| Connectivity | RS 232 Serial port, RS 485 Modbus-RTU serial ports |